174 Parameters
44.05
Ontime2 func
Configures on-time counter 2. This counter runs whenever
the signal selected by parameter
is on.
After the limit set by parameter
is
reached, an alarm specified by parameter
is given, and the counter reset.
The current value of the counter is readable from parameter
. Bit 1 of
indicates that the count has exceeded the limit.
44.06
Ontime2 src
Selects the signal to be monitored by on-time counter 2. See
parameter
.
RO1
Relay output RO1 (as indicated by
, bit 0).
1073742338
Running
1073939969
Charged
1074333186
Const
). -
Pointer
44.07
Ontime2 limit
Sets the alarm limit for on-time counter 2. See parameter
0 … 2147483647 s
Alarm limit for on-time counter 2.
1 = 1 s
44.08
Ontime2 alm sel
Selects the alarm for on-time counter 2. See parameter
On-time2
Pre-selectable alarm for on-time counter 2.
0
Device clean
Pre-selectable alarm for on-time counter 2.
1
Add cool fan
Pre-selectable alarm for on-time counter 2.
2
Cabinet fan
Pre-selectable alarm for on-time counter 2.
3
Dc-capacitor
Pre-selectable alarm for on-time counter 2.
4
Mot bearing
Pre-selectable alarm for on-time counter 2.
5
No.
Name/Value
Description
FbEq
Bit
Function
0
Counter mode
0 = Loop: If alarm is enabled by bit 1, the alarm stays active only for 10 seconds.
1 = Saturate: If alarm is enabled by bit 1, the alarm stays active until reset.
1
Alarm ena (Alarm enable)
0 = Disable: No alarm is given when limit is reached.
1 = Enable: Alarm is given when limit is reached.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program...
Page 2: ......
Page 4: ......
Page 24: ...24 Start up...
Page 28: ...28 Control locations and operating modes...
Page 252: ...252 Fieldbus control...