Parameters 145
Alarm
The drive generates alarm SAFE TORQUE OFF.
2
No
No action taken.
3
30.08
Cross connection
Selects how the drive reacts to incorrect input power and
motor cable connection (i.e. input power cable is connected
to drive motor connection).
No
No action taken.
0
Fault
The drive trips on fault CABLE CROSS CON.
1
30.09
Stall function
Selects how the drive reacts to a motor stall condition. The
protection wakes up if
• the drive is at stall current limit (defined by parameter
or
differs from 0
• the output frequency is below the level set by parameter
, and
• the conditions above have been valid longer than the time
set by parameter
.
See section
Stall protection (parameters 30.09…30.12)
page
30.10
Stall curr lim
Stall current limit in percent of the nominal current of the
motor. See parameter
0.0 … 1600.0%
Stall current limit.
10 = 1%
30.11
Stall freq hi
Stall frequency limit. See parameter
.
0.5 … 1000.0 Hz
Stall frequency limit.
10 = 1 Hz
30.12
Stall time
Stall time. See parameter
.
0 … 3600 s
Stall time.
1 = 1 s
31
31 Mot therm prot
Motor temperature measurement and thermal protection
settings.
31.01
Mot temp1 prot
Selects how the drive reacts when motor overtemperature is
detected by motor thermal protection 1.
No
Motor thermal protection 1 inactive.
0
Alarm
The drive generates alarm MOTOR TEMPERATURE when
the temperature exceeds the alarm level defined by
parameter
1
Fault
The drive generates alarm MOTOR TEMPERATURE or trips
on fault MOTOR OVERTEMP when the temperature exceeds
the alarm/fault level defined by parameter
(whichever is lower).
2
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm upon a stall condition.
2
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault upon a stall condition.