Parameters 167
36.23
Timed func3
Selects which time periods (1…4) are used with timed
function 3. Also determines whether boost is used with timed
function 3.
The parameter is a 16-bit word with each bit corresponding to
a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
36.24
Timed func4
Selects which time periods (1…4) are used with timed
function 4. Also determines whether boost is used with timed
function 4.
The parameter is a 16-bit word with each bit corresponding to
a function. Whenever a bit is set to 1, the corresponding
function is in use.
The bits of the binary number correspond to the following
functions:
38
38 Flux ref
Flux reference and
U/f
curve settings. See also section
38.01
Flux ref
Sets the flux reference (in percent of parameter
) at field weakening point.
0 … 200%
Flux reference at field weakening point.
1 = 1%
38.03
U/f curve func
Selects the form of the
U/f
(voltage/frequency) curve below
the field weakening point.
Linear
Linear
U/f
curve. Recommended for constant-torque
applications.
0
Quadratic
Quadratic
U/f
curve. Recommended for centrifugal pump and
fan applications.
1
User
Custom
U/f
curve. The curve is formed by the points defined
2
38.04
U/f curve freq1
Defines the frequency at the 1st point on the custom
U/f
curve
in percent of parameter
1 … 500%
1st point, frequency.
1 = 1%
38.05
U/f curve freq2
Defines the frequency at the 2nd point on the custom
U/f
curve in percent of parameter
.
1 … 500%
2nd point, frequency.
1 = 1%
No.
Name/Value
Description
FbEq
Bit
Function
0
Timer1 ena (Time period 1 enable)
1
Timer2 ena (Time period 2 enable)
2
Timer3 ena (Time period 3 enable)
3
Timer4 ena (Time period 4 enable)
4
Boost ena (Boost enable)
Bit
Function
0
Timer1 ena (Time period 1 enable)
1
Timer2 ena (Time period 2 enable)
2
Timer3 ena (Time period 3 enable)
3
Timer4 ena (Time period 4 enable)
4
Boost ena (Boost enable)