90 Parameters
13.04
AI1 max scale
Defines the real value that corresponds to the maximum
analogue input AI1 value defined by parameter
-32768.000 …
32768.000
Real value corresponding to maximum AI1 value.
1000 = 1
13.05
AI1 min scale
Defines the real value that corresponds to the minimum
analogue input AI1 value defined by parameter
. See the drawing at parameter
-32768.000
…32768.000
Real value corresponding to minimum AI1 value.
1000 = 1
13.06
AI2 filt time
Defines the filter time constant for analogue input AI2. See
parameter
.
0.000 … 30.000 s
Filter time constant.
1000 = 1 s
13.07
AI2 max
Defines the maximum value for analogue input AI2. The input
type is selected with jumper J2 on the JCU Control Unit.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI2 maximum value.
1000 = 1 unit
13.08
AI2 min
Defines the minimum value for analogue input AI2. The input
type is selected with jumper J2 on the JCU Control Unit.
-22.000 … 22.000
mA or
-11.000 … 11.000 V
AI2 minimum value.
1000 = 1 unit
No.
Name/Value
Description
FbEq
AI
(scaled)
AI
(mA/V)