Fault tracing 227
2005
MOTOR
TEMPERATURE
(0x4310)
Programmable fault:
Estimated motor temperature
(based on motor thermal
model) has exceeded alarm
limit defined by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters
…
).
Measured motor temperature
has exceeded alarm limit
defined by parameter
.
Check that actual number of sensors
corresponds to value set by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
2006
EMERGENCY OFF
(0xF083)
Drive has received emergency
OFF2 command.
To restart drive, activate Run enable
signal (source selected by parameter
) and start drive.
2007
RUN ENABLE
(0xFF54)
No Run enable signal is
received.
Check setting of parameter
. Switch signal on (e.g. in the
fieldbus Control Word) or check wiring of
selected source.
2008
ID-RUN
(0xFF84)
Motor identification run is on.
This alarm belongs to normal start-up
procedure. Wait until drive indicates that
motor identification is completed.
Motor identification is required. This alarm belongs to normal start-up
procedure.
Select how motor identification should be
performed, parameter
.
Start identification routines by pressing
Start key.
2009
EMERGENCY STOP
(0xF081)
Drive has received emergency
stop command (OFF1/OFF3).
Check that it is safe to continue
operation.
Return emergency stop push button to
normal position (or adjust the fieldbus
Control Word accordingly).
Restart drive.
2011
BR OVERHEAT
(0x7112)
Brake resistor temperature has
exceeded alarm limit defined
by parameter
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameters
Check alarm limit setting, parameter
.
Check that braking cycle meets allowed
limits.
2012
BC OVERHEAT
(0x7181)
Brake chopper IGBT
temperature has exceeded
internal alarm limit.
Let chopper cool down.
Check resistor overload protection
function settings (parameters
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Code
Alarm
(fieldbus code)
Cause
What to do