148 Parameters
KTY 2nd FEN
The temperature is supervised using a KTY84 sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
Note:
This selection does not apply to FEN-01.
3
PTC JCU
The temperature is supervised using 1…3 PTC sensors
connected to drive thermistor input TH.
4
PTC 1st FEN
The temperature is supervised using a PTC sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 1 is used for the
temperature supervision.
5
PTC 2nd FEN
The temperature is supervised using a PTC sensor
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
6
Pt100 JCU x1
The temperature is supervised using a Pt100 sensor
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
7
Pt100 JCU x2
The temperature is supervised using two Pt100 sensors
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
8
Pt100 JCU x3
The temperature is supervised using three Pt100 sensors
connected to analog input AI1 and analog output AI1 on the
JCU Control Unit of the drive.
9
Pt100 Ext x1
The temperature is supervised using a Pt100 sensor
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
10
Pt100 Ext x2
The temperature is supervised using two Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
11
Pt100 Ext x3
The temperature is supervised using three Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive.
12
31.07
Mot temp2 almLim
Defines the alarm limit for the motor thermal protection 2
(when parameter
is set to either
0 … 200 °C
Motor overtemperature alarm limit.
1 = 1 °C
31.08
Mot temp2 fltLim
Defines the fault limit for the motor thermal protection 2 (when
parameter
0 … 200 °C
Motor overtemperature fault limit.
1 = 1 °C
31.09
Mot ambient temp
Defines the ambient temperature for the thermal protection
mode.
-60 … 100 °C
Ambient temperature.
1 = 1 °C
No.
Name/Value
Description
FbEq