144 Parameters
30.02
Speed ref safe
Defines the safe speed reference that is used with the
setting of supervision parameters
or
upon an alarm.
This speed is used when the parameter is set to
-30000 … 30000
rpm
Safe speed reference.
1 = 1 rpm
30.03
Local ctrl loss
Selects how the drive reacts to a control panel or PC tool
communication break.
No
No action taken.
0
Fault
Drive trips on fault LOCAL CTRL LOSS.
1
Spd ref Safe
The drive generates alarm LOCAL CTRL LOSS and sets the
speed to the speed defined by parameter
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
2
Last speed
The drive generates alarm LOCAL CTRL LOSS and freezes
the speed to the level the drive was operating at. The speed
is determined by the average speed over the previous 10
seconds.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
30.04
Mot phase loss
Selects how the drive reacts when a motor phase loss is
detected.
No
No action taken.
0
Fault
The drive trips on fault MOTOR PHASE.
1
30.05
Earth fault
Selects how the drive reacts when an earth fault or current
unbalance is detected in the motor or the motor cable.
No
No action taken.
0
Warning
The drive generates alarm EARTH FAULT.
1
Fault
The drive trips on fault EARTH FAULT.
2
30.06
Suppl phs loss
Selects how the drive reacts when a supply phase loss is
detected.
No
No action taken.
0
Fault
The drive trips on fault SUPPLY PHASE.
1
30.07
Sto diagnostic
Selects how the drive reacts when the drive detects that the
Safe Torque Off function is active while the drive is stopped.
The Safe Torque Off function disables the control voltage of
the power semiconductors of the drive output stage, thus
preventing the inverter from generating the voltage required
to rotate the motor. For the wiring of the Safe Torque Off
circuit, see the appropriate hardware manual.
Notes:
• This parameter is for supervision only. The Safe Torque Off
function can activate even when this parameter is set to
• Fault STO 1 LOST / STO 2 LOST is activated if safety
circuit signal 1/2 is lost when the drive is in stopped state
and this parameter is set to
Fault
The drive trips on fault SAFE TORQUE OFF.
1
No.
Name/Value
Description
FbEq