316 Control through the embedded fieldbus interface
Setting the drive control parameters
After the embedded fieldbus interface has been set up, check and adjust the drive
control parameters listed in the table below. The
Setting for fieldbus control
column
gives the value or values to use when the embedded fieldbus signal is the desired
source or destination for that particular drive control signal. The
Function/
Information
column gives a description of the parameter.
Parameter
Setting for
fieldbus control
Function/Information
CONTROL COMMAND SOURCE SELECTION
Selects fieldbus as the source for the start
and stop commands when EXT1 is selected
as the active control location.
Selects fieldbus as the source for the start
and stop commands when EXT2 is selected
as the active control location.
P.02.36.08
Selects the fault reset bit of signal
as the source for the fault reset
command of the drive.
Note:
To start and stop the drive through control location EXT1, set parameter
and
keep parameter
to its default value (C.FALSE).
SPEED REFERENCE SELECTION
Selects a reference received through the
embedded fieldbus interface as the speed
reference ref1 of the drive.
Selects a reference received through the
embedded fieldbus interface as the speed
reference ref2 of the drive.
Note:
To control the drive speed with fieldbus reference REF1, set parameter
, and keep parameters
and
to their default values (Speed and C.FALSE).
TORQUE REFERENCE SELECTION
Selects one of the references received
through the embedded fieldbus interface as
the torque reference ref1 of the drive.
Selects one of the references received
through the embedded fieldbus interface as
the torque reference ref2 of the drive.
Note:
To control the torque of the drive with fieldbus reference REF2, set parameter
to its default value (C.FALSE) and set
to Torque.
REFERENCE SCALING
Defines the fieldbus reference REF1 scaling.
Selects also the fieldbus actual signal act1
when set to
.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...