194 Parameters
Alarm
Drive running:
The drive trips on SAFE TORQUE OFF when one or both of
the STO signals is lost.
Drive stopped:
The drive generates a SAFE TORQUE OFF alarm if both
STO signals are absent. If only one of the signals is lost, the
drive trips on STO1 LOST or STO2 LOST.
2
No
Drive running:
The drive trips on SAFE TORQUE OFF when one or both of
the STO signals is lost.
Drive stopped:
No action if both STO signals are absent. If only one of the
signals is lost, the drive trips on STO1 LOST or STO2 LOST.
3
Only Alarm
The drive generates a SAFE TORQUE OFF alarm if both
STO signals are absent. If only one of the signals is lost, the
drive trips on STO1 LOST or STO2 LOST.
4
30.08
Cross connection
Selects how the drive reacts to incorrect input power and
motor cable connection (i.e. input power cable is connected
to drive motor connection).
No
No action taken.
0
Fault
The drive trips on fault CABLE CROSS CON.
1
30.09
Stall function
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive is at stall current limit (
)
, and
• the output frequency is below the level set by parameter
, and
• the conditions above have been valid longer than the time
set by parameter
See section
Stall protection (parameters 30.09…30.12)
page
.
30.10
Stall curr lim
Stall current limit in percent of the nominal current of the
motor. See parameter
0.0 … 1600.0%
Stall current limit.
10 = 1%
30.11
Stall freq hi
Stall frequency limit. See parameter
.
Note:
Setting the limit below 10 Hz is not recommended.
0.5 … 1000.0 Hz
Stall frequency limit.
10 = 1 Hz
30.12
Stall time
Stall time. See parameter
0 … 3600 s
Stall time.
1 = 1 s
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm upon a stall condition.
2
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault upon a stall condition.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...