112 Parameters
No.
Name/Value
Description
FbEq
Bit
Name
Value Information
Log.
Par.
(continued)
9
Jogging 1
1
Activate Jogging 1. See section
OR
0
Jogging 1 disabled.
10
Jogging 2
1
Activate Jogging 2. See section
OR
0
Jogging 2 disabled.
11
Remote
cmd
1
Fieldbus control enabled.
–
–
0
Fieldbus control disabled.
12
Ramp out
0
1
Force output of Ramp Function Generator to zero. The
drive ramps to a stop (current and DC voltage limits are
in force).
–
–
0
No action.
13
Ramp hold
1
Halt ramping (Ramp Function Generator output held).
–
–
0
No action.
14
Ramp in 0
1
Force input of Ramp Function Generator to zero.
–
–
0
No action.
15
Ext1 / Ext2
1
Switch to external control location EXT2.
OR
0
Switch to external control location EXT1.
16
Req
startinh
1
Activate start inhibit.
–
–
0
No start inhibit.
17
Local ctl
1
Request local control for Control Word. Used when the
drive is controlled from a PC tool or panel or local
fieldbus.
• Local fieldbus: Transfer to fieldbus local control
(control through Control Word or reference).
Fieldbus steals the control.
• Panel or PC tool: Transfer to local control.
–
–
0
Request external control.
18
FbLocal ref
1
Request fieldbus local control.
–
–
0
No fieldbus local control.
19…27 Reserved
28
CW B28
Freely programmable control bits. See parameters
…
–
–
29
CW B29
30
CW B30
31
CW B31
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...