Parameters 255
0.00000 …
10.00000 p.u
Quadrature axis inductance in per unit.
100000 =
1 p.u.
97.08
Pm flux user
Defines the permanent magnet flux.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 … 2.00000
p.u
Permanent magnet flux in per unit.
100000 =
1 p.u.
97.09
Rs user SI
Defines the stator resistance
R
S
of the motor model.
0.00000 …
100.00000 ohm
Stator resistance.
100000 =
1 ohm
97.10
Rr user SI
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 …
100.00000 ohm
Rotor resistance.
100000 =
1 ohm
97.11
Lm user SI
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00 …100000.00
mH
Main inductance.
100 = 1 mH
97.12
SigL user SI
Defines the leakage inductance
σ
L
S
.
Note:
This parameter is valid only for asynchronous motors.
0.00 …100000.00
mH
Leakage inductance.
100 = 1 mH
97.13
Ld user SI
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 …100000.00
mH
Direct axis inductance.
100 = 1 mH
97.14
Lq user SI
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 …100000.00
mH
Quadrature axis inductance.
100 = 1 mH
97.18
Signal injection
Enables signal injection. A high frequency alternating signal is
injected to the motor at the low speed region to improve the
stability of torque control. Signal injection can be enabled with
different amplitude levels.
Note:
Use as low a level as possible that gives satisfactory
performance. Signal injection cannot be applied to
asynchronous motors.
0…4
0 = Signal injection is disabled.
1 = Signal injection is enabled with an amplitude level of 5%.
2 = Signal injection is enabled with an amplitude level of 10%.
3 = Signal injection is enabled with an amplitude level of 15%.
4 = Signal injection is enabled with an amplitude level of 20%.
1 = 1
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...