Control through the embedded fieldbus interface 335
Actual signals for the DCU 32-bit profile
The DCU 32-bit profile supports the use of two fieldbus actual values, ACT1 and
ACT2. The actual values are 32-bit values consisting of two 16-bit words. The MSW
(Most significant word) is the integer part and the LSW (Least significant word) the
fractional part of the 32-bit value. A negative reference is formed by calculating the
two’s complement from the corresponding positive value of the integer part (MSW).
and
select the drive actual
signals for the fieldbus actual values ACT1 and ACT2 respectively as follows:
, drive parameters
select the drive parameters for the fieldbus actual value ACT1 and
ACT2 respectively.
, drive parameter
will be written
to fieldbus actual value.
will be written to
the fieldbus actual value.
The table below clarifies the relation between the value of drive parameter and
fieldbus actual value (no scaling).
Value of the selected drive signal
Corresponding fieldbus actual value
ACT1 or ACT2 [integer and fractional
part]
32767.65535
32767.65535
0
0
-32768.65535
-32768.65535