Parameters 235
50.12
FB comm speed
Selects the fieldbus communication speed. The default
selection is
. Lowering the speed reduces the CPU load.
The table below shows the read/write intervals for cyclic and
acyclic data with each parameter setting.
*Cyclic data onsists of fieldbus CW and SW, Ref1 and Ref2,
and Act1 and Act2.
**Acyclic data consists of the parameter data mapped to
parameter groups
.
Low
Low speed selected.
0
Normal
Normal speed selected.
1
High
High speed selected.
2
Very high
Very high speed selected.
3
50.15
Fb cw used
Selects the fieldbus Control Word which controls the drive.
Pointer
page
).
-
50.20
Fb main sw func
Selects the rule on the basis of which the drive defines the
value for
51
51 FBA settings
Fieldbus adapter-specific settings.
51.01
FBA type
Displays the type of the connected fieldbus adapter module.
0 = Fieldbus module is not found or is not properly connected,
or parameter
, 1 = FPBA-xx
PROFIBUS-DP adapter module, 32 = FCAN-xx CANopen
adapter module, 37 = FDNA-xx DeviceNet adapter module
51.02
FBA par2
are adapter module-specific. For
more information, see the
User’s Manual
of the fieldbus
adapter module. Note that not all of these parameters are
necessarily used.
-
…
…
…
…
51.26
FBA par26
See parameter
-
51.27
FBA par refresh
Validates any changed adapter module configuration
parameter settings. After refreshing, the value reverts
automatically to
Note:
This parameter cannot be changed while the drive is
running.
Done
Refreshing done.
0
Refresh
Refreshing.
1
No.
Name/Value
Description
FbEq
Selection
Cyclic*
Acyclic**
Low
10 ms
10 ms
Normal
2 ms
10 ms
High
500 us
2 ms
Very high
250 us
500 us
Bit
Name
Information
0
Run Enable
func
1 = Parameter only:
Drive writes value 1 to the bit when the external run enable signal (par.
) has value 1.
0 = Param AND Fb cw:
Drive writes value 1 to the bit when the external run enable signal (par.
bit 7 (Run enable) is 1.
Summary of Contents for ACS850 series