196 Parameters
PTC 2nd FEN
The temperature is supervised using 1...3 PTC sensors
connected to encoder interface module FEN-xx installed in
drive Slot 1/2. If two encoder interface modules are used,
encoder module connected to Slot 2 is used for the
temperature supervision.
6
Pt100 JCU x1
The temperature is supervised using a Pt100 sensor
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive.
The analog output feeds constant current through the sensor.
The sensor resistance increases as the motor temperature
rises, as does the voltage over the sensor. The temperature
measurement function reads the voltage through the analog
input and converts it to degrees centigrade.
7
Pt100 JCU x2
The temperature is supervised using two Pt100 sensors
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive. See
above.
8
Pt100 JCU x3
The temperature is supervised using three Pt100 sensors
connected to analog input AI1 and analog output AO1 on the
JCU Control Unit of the drive. See
above.
9
Pt100 Ext x1
The temperature is supervised using a Pt100 sensor
connected to the first available analog input and analog
output on I/O extensions installed on the drive. See
above.
10
Pt100 Ext x2
The temperature is supervised using two Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive. See
above.
11
Pt100 Ext x3
The temperature is supervised using three Pt100 sensors
connected to the first available analog input and analog
output on I/O extensions installed on the drive. See
above.
12
31.03
Mot temp1 almLim
Defines the alarm limit for motor thermal protection 1 (when
parameter
is set to either
or
0 … 200 °C
Motor overtemperature alarm limit.
1 = 1 °C
31.04
Mot temp1 fltLim
Defines the fault limit for the motor thermal protection 1 (when
parameter
0 … 200 °C
Motor overtemperature fault limit.
1 = 1 °C
31.05
Mot temp2 prot
Selects how the drive reacts when motor overtemperature is
detected by motor temperature protection 2.
No
Motor temperature protection 2 inactive.
0
Alarm
The drive generates alarm MOTOR TEMP2 when the
temperature exceeds the alarm level defined by parameter
1
Fault
The drive generates alarm MOTOR TEMP2 or trips on fault
MOTTEMP2 when the temperature exceeds the alarm/fault
level defined by parameter
(whichever is lower).
2
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...