218 Parameters
1 … 500%
2nd point, frequency.
1 = 1%
38.06
U/f curve freq3
Defines the frequency at the 3rd point on the custom
U/f
curve in percent of parameter
.
1 … 500%
3rd point, frequency.
1 = 1%
38.07
U/f curve freq4
Defines the frequency at the 4th point on the custom
U/f
curve in percent of parameter
.
1 … 500%
4th point, frequency.
1 = 1%
38.08
U/f curve freq5
Defines the frequency at the 5th point on the custom
U/f
curve in percent of parameter
.
1 … 500%
5th point, frequency.
1 = 1%
38.09
U/f curve volt1
Defines the voltage at the 1st point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
1st point, voltage.
1 = 1%
38.10
U/f curve volt2
Defines the voltage at the 2nd point on the custom
U/f
curve
in percent of parameter
0 … 200%
2nd point, voltage.
1 = 1%
38.11
U/f curve volt3
Defines the voltage at the 3rd point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
3rd point, voltage.
1 = 1%
38.12
U/f curve volt4
Defines the voltage at the 4th point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
4th point, voltage.
1 = 1%
38.13
U/f curve volt5
Defines the voltage at the 5th point on the custom
U/f
curve in
percent of parameter
.
0 … 200%
5th point, voltage.
1 = 1%
38.16
Flux ref pointer
Selects the source of the flux reference.
Pointer
Value pointer setting (see
on page
-
40
40 Motor control
Motor control settings.
40.01
Motor noise
An optimization setting for balancing between control
performance and motor noise level.
Cyclic
Control performance optimized for cyclic load applications.
Note:
With this setting, the maximum motor cable length is
smaller than with
0
Low noise
Minimizes motor noise; control performance optimized for
high (> 300 Hz) output frequencies.
Note:
Drive loadability is reduced with this setting and some
derating must be applied if a certain constant output current is
needed. This setting is not recommended for cyclic load
applications. The maximum motor cable length is 50 m
(164 ft) with drives up to 45 kW.
1
Default
Control performance optimized for long motor cables.
2
No.
Name/Value
Description
FbEq
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...