314 Control through the embedded fieldbus interface
Setting up the embedded fieldbus interface
Set the drive up for the embedded fieldbus communication with the parameters
shown in the table below. The
Setting for fieldbus control
column gives either the
value to use or the default value. The
Function/Information column
gives a
description of the parameter or instructs in its use.
Parameter
Setting for
fieldbus control
Function/Information
COMMUNICATION INITIALIZATION
P.02.36
Selects the address of the fieldbus Control
Word in use (
(default)
Initializes embedded fieldbus communication.
Drive-to-drive link operation (parameter group
57) is automatically disabled.
EMBEDDED MODBUS CONFIGURATION
1 (default)
Node address. There may not be two nodes
with the same node address online.
9600 (default)
Defines the communication speed of the link.
Use the same setting as in the master station.
(default)
Selects the parity and stop bit setting. Use the
same setting as in the master station.
58.06 Control profile ABB Enhanced
(default)
Selects the communication profile used by the
drive. See section
on page
.
600 (default)
Defines the timeout limit for the EFB
communication monitoring.
(default)
Enables/disables EFB communication loss
monitoring and defines the means for resetting
the counter of the communication loss delay.
(default)
Defines the drive operation after the EFB
communication loss monitoring awakes.
(default)
Refreshes the settings of parameters
0 (default)
Defines the delay time which the slave waits
until it sends a response.
(default)
Selects whether the drive returns Modbus
exception codes or not.
(default)
Defines the order of the data words in the
Modbus frame.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...