Parameters 205
34.02
Underload func
Configures the supervision of the lower boundary of the user
load curve.
34.03
Load freq1
Drive output frequency at point 1 of user load curve.
1 … 500 Hz
Frequency at point 1.
1 = 1 Hz
34.04
Load freq2
Drive output frequency at point 2 of user load curve.
1 … 500 Hz
Frequency at point 2.
1 = 1 Hz
34.05
Load freq3
Drive output frequency at point 3 of user load curve.
1 … 500 Hz
Frequency at point 3.
1 = 1 Hz
34.06
Load freq4
Drive output frequency at point 4 of user load curve.
1 … 500 Hz
Frequency at point 4.
1 = 1 Hz
34.07
Load freq5
Drive output frequency at point 5 of user load curve.
1 … 500 Hz
Frequency at point 5.
1 = 1 Hz
34.08
Load low lim1
Minimum load (current or torque) at point 1 of user load
curve.
0 … 1600%
Minimum load at point 1.
1 = 1%
34.09
Load low lim2
Minimum load (current or torque) at point 2 of user load
curve.
0 … 1600%
Minimum load at point 2.
1 = 1%
34.10
Load low lim3
Minimum load (current or torque) at point 3 of user load
curve.
0 … 1600%
Minimum load at point 3.
1 = 1%
34.11
Load low lim4
Minimum load (current or torque) at point 4 of user load
curve.
0 … 1600%
Minimum load at point 4.
1 = 1%
34.12
Load low lim5
Minimum load (current or torque) at point 5 of user load
curve.
0 … 1600%
Minimum load at point 5.
1 = 1%
34.13
Load high lim1
Maximum load (current or torque) at point 1 of user load
curve.
0 … 1600%
Maximum load at point 1.
1 = 1%
No.
Name/Value
Description
FbEq
Bit
Function
0
Ena sup (Enable supervision)
0 = Disabled: Supervision disabled.
1 = Enabled: Supervision enabled.
1
Input value sel (Input value selection)
0 = Current: Current is supervised.
1 = Torque: Torque is supervised.
2
Ena warn (Enable warning)
0 = Disabled
1 = Enabled: Drive generates an alarm when the load remains below the curve for longer
than the time defined by parameter
.
3
Ena fault (Enable fault)
0 = Disabled
1 = Enabled: Drive trips on a fault when the load remains below the curve for longer than
the time defined by parameter
.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...