292 Fault tracing
2012
BC OVERHEAT
(0x7181)
Brake chopper IGBT
temperature has exceeded
internal alarm limit.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameters
).
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
2013
DEVICE OVERTEMP
(0x4210)
Measured drive temperature
has exceeded internal alarm
limit.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against unit power.
2014
INTBOARD
OVERTEMP
(0x7182)
Interface board (between
power unit and control unit)
temperature has exceeded
internal alarm limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
2015
BC MOD OVERTEMP
(0x7183)
Input bridge or brake chopper
temperature has exceeded
internal alarm limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
2017
FIELDBUS COMM
(0x7510)
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module or between
PLC and fieldbus adapter
module is lost.
Check status of fieldbus communication.
See the appropriate
User’s Manual
of
fieldbus adapter module.
Check settings of parameter group
Check cable connections.
Check if communication master is able to
communicate.
2018
LOCAL CTRL LOSS
(0x5300)
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
2019
AI SUPERVISION
(0x8110)
Programmable fault:
An analogue input has reached
limit defined by parameter
Check analogue input source and
connections.
Check analogue input minimum and
maximum limit settings.
2020
FB PAR CONF
(0x6320)
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter group
Code
Alarm
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...