Fault tracing 293
2021
NO MOTOR DATA
(0x6381)
Parameters in group 99 have
not been set.
Check that all the required parameters in
group 99 have been set.
Note:
It is normal for this alarm to appear
during the start-up until the motor data is
entered.
2022
ENCODER 1
FAILURE (0x7301)
Encoder 1 has been activated
by parameter but the encoder
interface (FEN-xx) cannot be
found.
Check parameter
setting corresponds to actual encoder
interface 1 (FEN-xx) installed in drive
Slot 1/2 (parameter
/
Note:
The new setting will only take
effect after parameter
is used or after the JCU Control
Unit is powered up the next time.
2023
ENCODER 2
FAILURE (0x7381)
Encoder 2 has been activated
by parameter but the encoder
interface (FEN-xx) cannot be
found.
Check parameter
setting corresponds to actual encoder
interface 1 (FEN-xx) installed in drive
Slot 1/2 (parameter
/
Note:
The new setting will only take
effect after parameter
is used or after the JCU Control
Unit is powered up the next time.
2027
FEN TEMP MEAS
FAILURE
(0x7385)
Error in temperature
measurement when
temperature sensor (KTY or
PTC) connected to encoder
interface FEN-xx is used.
Check that parameter
/
setting
corresponds to actual encoder interface
installation (
/
If one FEN-xx module is used:
- Parameter
must be set either to
. The FEN-xx
module can be in either Slot 1 or Slot 2.
If two FEN-xx modules are used:
- When parameter
is set to
or
, the encoder
installed in drive Slot 1 is used.
- When parameter
is set to
or
, the encoder
installed in drive Slot 2 is used.
Error in temperature
measurement when KTY
sensor connected to encoder
interface FEN-01 is used.
FEN-01 does not support temperature
measurement with KTY sensor. Use PTC
sensor or other encoder interface
module.
Code
Alarm
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...