Fault tracing 303
0032
OVERSPEED
(0x7310)
Motor is turning faster than
highest allowed speed due to
incorrectly set minimum/
maximum speed, insufficient
braking torque or changes in
load when using torque
reference.
Check minimum/maximum speed
settings, parameters
and
.
Check adequacy of motor braking torque.
Check applicability of torque control.
Check need for brake chopper and
resistor(s).
0033
BRAKE START
TORQUE
(0x7185)
Programmable fault:
Mechanical brake fault. Fault is
activated if required motor
starting torque (
) is not achieved.
Check brake open torque setting,
parameter
Check drive torque and current limits.
See parameter group
.
0034
BRAKE NOT
CLOSED
(0x7186)
Programmable fault:
Mechanical brake control fault.
Activated e.g. if brake
acknowledgement is not as
expected during brake closing.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
.
To determine whether problem is with
acknowledgement signal or brake, check
if brake is closed or open.
0035
BRAKE NOT OPEN
(0x7187)
Programmable fault:
Mechanical brake control fault.
Activated e.g. if brake
acknowledgement is not as
expected during brake
opening.
Check mechanical brake connection.
Check mechanical brake settings in
parameter group
.
To determine whether problem is with
acknowledgement signal or brake, check
if brake is closed or open.
0036
LOCAL CTRL LOSS
(0x5300)
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
0037
NVMEM
CORRUPTED
(0x6320)
Drive internal fault.
Note:
This fault cannot be
reset.
Check the fault logger for a fault code
extension. See appropriate actions for
each extension below.
*Refer to Application programming for
ACS850 drives (3AUA0000078664
[English]).
Extension: 2051
Total number of parameters
(including unused space
between parameters) exceeds
firmware maximum.
*Move parameters from the firmware
groups to the application groups.
*Reduce the number of parameters.
Extension: Other
Drive internal fault.
Contact your local ABB representative.
0038
OPTIONCOMM LOSS
(0x7000)
Communication between drive
and option module (FEN-xx
and/or FIO-xx) is lost.
Check that option modules are properly
connected to Slot 1 and (or) Slot 2.
Check that option modules or Slot 1/2
connectors are not damaged. To
determine whether module or connector
is damaged: Test each module
individually in Slot 1 and Slot 2.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...