Application macros 91
Default control connections for the Factory macro
External power input
24 V DC, 1.6 A
XPOW
+24VI
1
GND
2
Relay output RO1 [Ready]
250 V AC / 30 V DC
2 A
XRO1
NO
1
COM
2
NC
3
Relay output RO2 [Modulating]
250 V AC / 30 V DC
2 A
XRO2
NO
4
COM
5
NC
6
Relay output RO3 [Fault (-1)]
250 V AC / 30 V DC
2 A
XRO3
NO
7
COM
8
NC
9
+24 V DC
XD24
+24VD
1
Digital input ground
DIGND
2
+24 V DC
+24VD
3
Digital input/output ground
DIOGND
4
DI/DIO grounding selection jumpers
Digital input DI1 [Stop/Start]
XDI
DI1
1
Digital input DI2
DI2
2
Digital input DI3 [Reset]
DI3
3
Digital input DI4
DI4
4
Digital input DI5
DI5
5
Digital input DI6 or thermistor input
DI6
6
Start interlock (0 = Stop)
DIIL
A
Digital input/output DIO1 [Output: Ready]
XDIO
DIO1
1
Digital input/output DIO2 [Output: Running]
DIO2
2
Reference voltage (+)
XA
I
+VREF
1
Reference voltage (–)
-VREF
2
Ground
AGND
3
Analog input AI1 [Speed reference 1]
(Current or voltage, selectable by jumper AI1)
AI1+
4
AI1-
5
Analog input AI2 (Current or voltage, selectable by jumper AI2)
AI2+
6
AI2-
7
AI1 current/voltage selection jumper
AI1
AI2 current/voltage selection jumper
AI2
Analog output AO1 [Current %]
XAO
AO1+
1
AO1-
2
Analog output AO2 [Speed %]
AO2+
3
AO2-
4
Drive-to-drive link termination jumper
T
Drive-to-drive link
XD2D
B
1
A
2
BGND
3
Safe torque off. Both circuits must be closed for the drive to start.
XST
O
OUT1
1
OUT2
2
IN1
3
IN2
4
Control panel connection
Memory unit connection
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...