294 Fault tracing
2030
RESOLVER
AUTOTUNE ERR
(0x7388)
Resolver autotuning routines,
which are automatically started
when resolver input is
activated for the first time,
have failed.
Check cable between resolver and
resolver interface module (FEN-21) and
order of connector signal wires at both
ends of cable.
Check resolver parameter settings.
For resolver parameters and information,
see parameter group
Note:
Resolver autotuning routines
should always be performed after
resolver cable connection has been
modified. Autotuning routines can be
activated by setting parameter
, and
then setting parameter
.
2031
ENCODER 1 CABLE
(0x7389)
Encoder 1 cable fault detected. Check cable between FEN-xx interface
and encoder 1. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
2032
ENCODER 2 CABLE
(0x738A)
Encoder 2 cable fault detected. Check cable between FEN-xx interface
and encoder 2. After any modifications in
cabling, re-configure interface by
switching drive power off and on, or by
activating parameter
2033
D2D
COMMUNICATION
(0x7520)
Programmable fault:
On the master drive: The drive
has not been replied to by an
activated follower for five
consecutive polling cycles.
Check that all drives that are polled
(parameters
) on the drive-to-
drive link are powered, properly
connected to the link, and have the
correct node address.
Check the drive-to-drive link wiring.
On a follower drive: The drive
has not received new
reference 1 and/or 2 for five
consecutive reference
handling cycles.
Check the settings of parameters
master drive.
Check the drive-to-drive link wiring.
2034
D2D BUFFER
OVERLOAD
(0x7520)
Programmable fault:
Transmission of drive-to-drive
references failed because of
message buffer overflow.
Contact your local ABB representative.
2035
PS COMM
(0x5480)
Communication errors
detected between the JCU
Control Unit and the power unit
of the drive.
Check the connections between the JCU
Control Unit and the power unit.
2036
RESTORE
(0x6300)
Restoration of backed-up
parameters failed.
Contact your local ABB representative.
2037
CUR MEAS
CALIBRATION
(0x2280)
Current measurement
calibration will occur at next
start.
Informative alarm.
2038
AUTOPHASING
(0x3187)
Autophasing will occur at next
start.
Informative alarm.
Code
Alarm
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...