302 Fault tracing
0021
STO1 LOST
(0x8182)
Safe torque off function is
active, i.e. safety circuit signal
1 connected between XSTO:1
and XSTO:3 is lost.
Check safety circuit connections. For
more information, see the appropriate
drive
Hardware Manual
, description of
parameter
(page
), and
Application guide - Safe torque off
function for ACSM1, ACS850 and
ACQ810 drives
(3AFE68929814
[English]).
0022
STO2 LOST
(0x8183)
Safe torque off function is
active, i.e. safety circuit signal
2 connected between XSTO:2
and XSTO:4 is lost.
0023
STO MODE CHANGE
(0xFF7A)
Error in changing Safe torque
off supervision, i.e. parameter
setting
could not be changed to value
Contact your local ABB representative.
0024
INTBOARD
OVERTEMP
(0x7182)
Interface board (between
power unit and control unit)
temperature has exceeded
internal fault limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
0025
BC MOD OVERTEMP
(0x7183)
Input bridge or brake chopper
temperature has exceeded
internal fault limit.
Let drive cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
0026
AUTOPHASING
(0x3187)
Autophasing routine (see
section
on page
) failed.
Try other autophasing modes (see
parameter
) if
possible.
0027
PU LOST
(0x5400)
Connection between the JCU
Control Unit and the power unit
of the drive is lost.
Check the connections between the JCU
Control Unit and the power unit.
0028
PS COMM
(0x5480)
Communication errors
detected between the JCU
Control Unit and the power unit
of the drive.
Check the connections between the JCU
Control Unit and the power unit.
0030
EXTERNAL
(0x9000)
Fault in external device. (This
information is configured
through one of programmable
digital inputs.)
Check external devices for faults.
Check parameter
setting.
0031
SAFE TORQUE OFF
(0xFF7A)
Programmable fault:
Safe torque off function is
active, i.e. safety circuit
signal(s) connected to
connector XSTO is lost during
start or run, or while drive is
stopped and parameter
.
Check safety circuit connections. For
more information, see the appropriate
drive
Hardware Manual
, and
Application
guide - Safe torque off function for
ACSM1, ACS850 and ACQ810 drives
(3AFE68929814 [English]).
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...