110 Parameters
02.31
D2D follower cw
Drive-to-drive control word sent to the followers by default.
See also parameter group
on page
-
02.32
D2D ref1
Drive-to-drive reference 1 received from the master.
1 = 1
02.33
D2D ref2
Drive-to-drive reference 2 received from the master.
1 = 1
02.34
Panel ref
Reference given from the control panel. See also parameter
100 = 1 rpm
10 = 1%
02.35
FEN DI status
Status of the digital inputs of FEN-xx encoder interfaces in
drive option slots 1 and 2. Examples:
000001 (01h) = DI1 of FEN-xx in slot 1 is ON, all others are
OFF.
000010 (02h) = DI2 of FEN-xx in slot 1 is ON, all others are
OFF.
010000 (10h) = DI1 of FEN-xx in slot 2 is ON, all others are
OFF.
100000 (20h) = DI2 of FEN-xx in slot 2 is on, all others are
OFF.
-
No.
Name/Value
Description
FbEq
Bit
Information
0
Stop.
1
Start.
2 … 6
Reserved.
7
Run enable.
8
Reset.
9 … 14 Freely assignable through bit pointer settings.
15
EXT1/EXT2 selection. 0 = EXT1 active, 1 = EXT2 active.
Summary of Contents for ACS850 series