306 Fault tracing
0061
SPEED FEEDBACK
(0x8480)
No speed feedback is
received.
Check the settings of the parameters in
group
Check encoder installation. See the
description of fault 0039 (ENCODER1)
for more information.
0062
D2D SLOT COMM
(0x7584)
Drive-to-drive link is set to use
an FMBA module for
communication, but no module
is detected in specified slot.
Check the settings of parameters
and
. Ensure that the FMBA
module has been detected by checking
parameters
.
Check that the FMBA module is correctly
wired.
Try installing the FMBA module into
another slot. If the problem persists,
contact your local ABB representative.
0063
MOTOR TEMP2
(0x4313)
Programmable fault:
Estimated motor temperature
(based on motor thermal
model) has exceeded fault limit
defined by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
Check motor thermal model settings
(parameters
).
Measured motor temperature
has exceeded fault limit
defined by parameter
.
Check that actual number of sensors
corresponds to value set by parameter
.
Check motor ratings and load.
Let motor cool down. Ensure proper
motor cooling: Check cooling fan, clean
cooling surfaces, etc.
Check value of alarm limit.
0064
IGBT OVERLOAD
(0x5482)
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short circuit
in the motor cable.
Check motor cable.
0065
IGBT TEMP
(0x4210)
Drive IGBT temperature is
excessive.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
0066
COOLING
(0x4290)
Drive module temperature is
excessive.
Check setting of parameter
.
Check ambient temperature. If it exceeds
40 °C (104 °F), ensure that load current
does not exceed derated load capacity of
drive. See the appropriate
Hardware
Manual.
Check drive module cooling air flow and
fan operation.
Check inside of cabinet and heatsink of
drive module for dust pick-up. Clean
whenever necessary.
0067
FPGA ERROR1
(0x5401)
Drive internal fault
Contact your local ABB representative.
0068
FPGA ERROR2
(0x5402)
Drive internal fault
Contact your local ABB representative.
Code
Fault
(fieldbus code)
Cause
What to do
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...