124 Parameters
09
09 System info
Drive type, program revision and option slot occupation
information.
09.01
Drive type
Displays the drive type (for example, ACS850).
-
09.02
Drive rating ID
Displays the inverter type (ACS850-xx-…) of the drive.
0 = Unconfigured, 101 = 03A0, 102 = 03A6, 103 = 04A8,
104 = 06A0, 105 = 08A0, 106 = 010A, 107 = 014A,
108 = 018A, 109 = 025A, 110 = 030A, 111 = 035A,
112 = 044A, 113 = 050A, 114 = 061A, 115 = 078A,
116 = 094A, 117 = 103A, 118 = 144A, 119 = 166A,
120 = 202A, 121 = 225A, 122 = 260A, 123 = 290A,
124 = 430A, 125 = 521A, 126 = 602A, 127 = 693A,
128 = 720A, 141 = 03A0_2, 142 = 03A6_2, 143 = 04A8_2,
144 = 06A0_2, 145 = 08A0_2, 146 = 010A_2, 147 = 014A_2,
148 = 018A_2, 149 = 025A_2, 150 = 030A_2, 151 = 035A_2,
152 = 044A_2, 153 = 050A_2, 154 = 061A_2, 155 = 078A_2,
156 = 094A_2
1 = 1
09.03
Firmware ID
Displays the firmware name. E.g. UIFI.
-
09.04
Firmware ver
Displays the version of the firmware package in the drive, e.g.
E00F hex.
-
09.05
Firmware patch
Displays the version of the firmware patch in the drive.
1 = 1
09.10
Int logic ver
Displays the version of the logic on the main circuit board of
the drive.
-
09.20
Option slot1
Displays the type of the optional module in option slot 1.
0 = No option, 1 = No comm, 2 = Unknown, 3 = FEN-01,
4 = FEN-11, 5 = FEN-21, 6 = FIO-01, 7 = FIO-11,
8 = FPBA-01, 9 = FPBA-02, 10 = FCAN-01, 11 = FDNA-01,
12 = FENA-01, 13 = FENA-02, 14 = FLON-01,
15 = FRSA-00, 16 = FMBA-01, 17 = FFOA-01,
18 = FFOA-02, 19 = FSEN-21, 20 = FEN-31, 21 = FIO-21,
22 = FSCA-01, 23 = FSEA-21, 24 = FIO-31, 25 = FECA-01
1 = 1
09.21
Option slot2
Displays the type of the optional module in option slot 2. See
signal
1 = 1
09.22
Option slot3
Displays the type of the optional module in option slot 3. See
signal
1 = 1
10
10 Start/stop/dir
Start/stop/direction etc. signal source selections.
10.01
Ext1 start func
Selects the source of start and stop commands for external
control location 1 (EXT1).
Note:
This parameter cannot be changed while the drive is
running.
Not sel
No start or stop command sources selected.
0
In1
The source of the start and stop commands is selected by
parameter
. The state transitions of the
source bit are interpreted as follows:
1
No.
Name/Value
Description
FbEq
State of source
(via par
Command
0 -> 1
Start
1 -> 0
Stop
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...