242 Parameters
None
EFB communication loss monitoring is disabled.
0
Any message
EFB communication loss monitoring is enabled. Any Modbus
request resets the timeout counter.
1
Ctrl write
EFB communication loss monitoring is enabled. Writing to
control or reference word resets the timeout counter.
2
58.09
Comm loss action
Defines the drive operation after the EFB communication loss
monitoring awakes. See parameters
and
None
No action.
0
Fault
Drive trips on a fault (EFB COMM LOSS).
1
Safe speed
Drive generates an alarm (EFB COMM LOSS) and takes the
safe speed into use (see parameter
2
Last speed
Drive generates an alarm (EFB COMM LOSS) and takes the
last speed into use (average over the previous 10 seconds).
3
58.10
Refresh settings
Refreshes the settings of parameters
…
Done
Initial value. The value is restored after the refresh is done.
0
Refresh
Refresh.
1
58.11
Reference scale
Defines the factor which the DCU 16-bit communication
profile uses when scaling fieldbus references to drive
references and drive actual values to fieldbus actual signals.
The references are multiplied by this scaling factor. See
section
on page
.
1…65535
Scaling factor.
1 = 1
58.15
Comm diagnostics
16-bit packed boolean data word for the communication
diagnostics flag bits. Read only.
0x0000…0xFFFF
Data word (hex).
1 = 1
No.
Name/Value
Description
FbEq
Bit
Information
0
Reserved.
1
NotThisNodeData (Last received packet was not for this node.)
2
Reserved.
3
One ok packet (At least one packet has been successfully received after the power up.)
4
Reserved.
5
Comm timeout (Communication time-out has occured.)
6
Not used.
7
Not used.
8
Last write was not successful because of a parameter value limit violation.
9
Last read was not successful because only one register was used to read a 32-bit value.
10
Last write was not successful because the parameter was read only.
11
Last parameter access was not successful because the parameter or group did not exist.
12
Not used.
13
Not used.
14
Not used.
15
Last write was not successful because only one register was used to read a 32-bit value.
16…31 Not used.
Summary of Contents for ACS850 series
Page 1: ...ACS850 Firmware Manual ACS850 Standard Control Program ...
Page 4: ......
Page 56: ...56 Control locations and operating modes ...
Page 262: ...262 Parameters ...
Page 310: ...310 Fault tracing ...
Page 348: ...348 Control through a fieldbus adapter ...
Page 358: ...358 Drive to drive link ...