80 Standard Commissioning Process
Control from overriding system
Two external control locations EXT1 and EXT2 are available.
The user can select the sources of the MCB open and MCB close commands separately
for each location by parameters 82.20 MCB Ext1 commands and 82.21 MCB Ext2
commands.
The user can select the sources of the start and stop commands separately for each
location by parameters 20.01…20.10.
The operating mode can be selected separately for each location, which enables quick
switching between different operating modes, for example speed and torque control.
Selection between EXT1 and EXT2 is done via any binary source such as a digital input or
fieldbus control word (see parameter 19.11 Ext1/Ext2 selection).
The source of reference is selectable for each operating mode separately. For speed
reference setting go to parameter group 23 if Rpm is used, or parameter group 28 if Hz is
used. For fieldbus setting, go to parameter group 50, 51, 52, 53.
•
Release the local control button on DriveStartup, only record the graph in this step.
•
Check the parameters are correctly set regarding external control.
a. The I/O termianls (digital and analog inputs), or optional I/O extension modules
b. An optional fieldbus adapter module
c. Other requirement.
•
Control the drive by overriding system.
•
Add additional signals to the graph if necessary
.
NOTICE
Don’t select the application macro by setting 96.04 Macro select, because it
will reset some of parameters which had been changed to default value. Change
corresponding parameters. Only FBA A is for use. FBA B is used internally for IO
Controller in slot 2.
Summary of Contents for ACS580MV
Page 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Page 4: ......
Page 8: ...8 ...
Page 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Page 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Page 83: ...Standard Commissioning Process 83 ...
Page 96: ...96 Standard Commissioning Process ...
Page 121: ...Option 121 IO signals ...
Page 122: ...122 Option Panel control interface System fault ...
Page 140: ...140 Option ...
Page 148: ...148 Preventive Maintenance ...