Standard Commissioning Process 71
b. Start/Stop/Direction, in parameter group 20.
c. Start/Stop mode, in parameter group 21.
d. Speed reference ramp, in parameter group 23.
e. Frequency reference chain, in parameter group 28.
f. Protection, in parameter group 34.
Note:
Generally, the protection parameters need to be set as default, do not modify
unless receive the permission from MV Drives Supportline.
•
Motor thermal protection, if need (motor temperature, cable temperature, motor
cooling fan), in parameter group 35.
•
Energy efficiency, in parameter group 45.
•
Monitoring and scaling, in parameter group 46.
•
Internal fieldbus settings, in parameter group 54.
Note:
Only save and set, active default setting IO controller.
•
Local control disable, in parameter group 81.
Note:
Including the logic test, refer to the DriveStartup.
•
MCB available / MCB ON prevention / MCB external protection monitoring, in
parameter group 82.
Note:
Including the logic test, refer to the DriveStartup.
•
For particular parameter description refer to the
ACS580MV Firmware Manual
(3BHS811381).
Summary of Contents for ACS580MV
Page 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Page 4: ......
Page 8: ...8 ...
Page 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Page 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Page 83: ...Standard Commissioning Process 83 ...
Page 96: ...96 Standard Commissioning Process ...
Page 121: ...Option 121 IO signals ...
Page 122: ...122 Option Panel control interface System fault ...
Page 140: ...140 Option ...
Page 148: ...148 Preventive Maintenance ...