20 Standard Commissioning Process
•
The connection to system ground has to be established in compliance with local
regulations.
Main circuit breaker (MCB)
•
The type of MCB is selected as per
ACS580MV Engineering Guideline
(2UBB013672).
•
The MCB is ready to be tested with the converter.
•
The MCB protection relay settings are set and tested, and it can be modified by
requirement of commissioning engineer.
•
Safety devices (door locks etc.) are tested and in operation.
•
Local operation of MCB is disabled, and the connection to switch or button is
canceled.
•
The wiring of the control & signal cables connecting with the converter is finished.
•
The user manual and technical specification is available.
•
Withstand voltage test of the MCB have been done according to manufacture
specifications. The official test report must be available.
Bolt size
Bolt type
Tightening torque (Nm)
M3
Copper
0.8
M4
Steel/ Stainless steel
2
Copper
1.2
M5
Steel/ Stainless steel
3
Copper
2
M6
Steel/ Stainless steel
5.5
Copper
3
M8
Steel/ Stainless steel
10 (aluminum busbar)/ 15(copper busbar)
Copper
6
M10
Steel/ Stainless steel
20 (aluminum busbar)/ 30(copper busbar)
Copper
10
M12
Steel/ Stainless steel
30 (aluminum busbar)/ 40(copper busbar)
Copper
15.5
M16
Steel/ Stainless steel
90 (aluminum busbar)/ 120(copper busbar)
Copper
30
M20
Steel/ Stainless steel
120 (aluminum busbar)/ 160(copper busbar)
Copper
52
Summary of Contents for ACS580MV
Page 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Page 4: ......
Page 8: ...8 ...
Page 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Page 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Page 83: ...Standard Commissioning Process 83 ...
Page 96: ...96 Standard Commissioning Process ...
Page 121: ...Option 121 IO signals ...
Page 122: ...122 Option Panel control interface System fault ...
Page 140: ...140 Option ...
Page 148: ...148 Preventive Maintenance ...