54 Standard Commissioning Process
•
Please operate the converter according to the description of “DriveStartup”.
Loading the DSP software manually to power modules
•
Necessary tools: 5.5 VDC power, USB to POF cable and fiber cable.
•
Install the Tera term programing tool, select the default components.
•
Check and confirm the drive has been discharged and door lock is released.
•
Open the INU door and then switch off the control power supply.
•
Connect the POF link to power module and USB to PC.