Standard Commissioning Process 81
•
Observe and save the measurement, attach plot to report.
Motor ramp up and down with load
DANGER
indicates a hazardous situation which, if not avoided, will result in
death or serious injury.After the motor has been coupled and run with the driven
equipment, all interlocks from an overriding control system must be in
operation.These interlocks should stop the drive if a critical condition occurs in the
process.If the trip levels, acceleration or deceleration times are set wrong it may cause
mechanical damages on the application or interrupt the process.