Chapter 2 Alarm Message
Cause
The rack temperature is higher than the set single high threshold.
Influence
This leads to the abnormal working of the switch.
Recommended
Operations
Lower the environment temperature of the rack by using fan heat
dissipation.
Alarm Prototype
Description
Alarm occured
Current
temperature
is
%dC/%dF,exceeds
the
thresh-
old(%dC/%dF)
Alarm cleared
Current temperature is %dC/%dF,under the threshold(%dC/%dF)
The first %d is the environment Centigrade degree; the second
%d is the Fahrenheit degree; the third %d is the environment
Centigrade degree of the set threshold; the fourth %d is the envi-
ronment Fahrenheit degree of the set threshold.
Alarm occured
16:20:31 06/26/2008 UTC alarm 73 occurred %ENVIRON-
MENT% Current temperature is 90C/194F,exceeds the thresh-
old(80C/176F)
Alarm cleared
16:22:11 06/26/2008 UTC alarm 73 cleared %ENVIRONMENT%
Current temperature is 80C/176F,under the threshold(90C/194F)
Alarm Description
The rack temperature is higher than the set single high threshold.
Supported Devices
ZXR10 3900/3200, 5900/5200 and G-series switch.
Appendix
Specification
N.A.
74
Message No.
74
Default Severity
Level
5
Alarm Recovery
Available
Alarm Type
Environmental Alarm
NM Level
3
Cause
The power works abnormally.
Influence
This leads to the abnormal working of the switch.
Recommended
Operations
Check whether the power input is normal and whether the rack
output is normal; whether the power module is plugged correctly;
whether the connection is OK.
Alarm Prototype
Description
Alarm occured
Power%d do not work!
Alarm cleared
Power%d restart!
% d: the power serial number. Multiple power states can be dis-
played simultaneously.
UAS10800E:
Confidential and Proprietary Information of ZTE CORPORATION
17