Table B.15 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0180
4
o
0216
4
o
0240
4
o
0302
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
A5
A6
A7
A8
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
90 (125)
110
(150)
110
(150)
132
(175)
132
(175)
150
(200)
150
(200)
185
(250)
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
b8-03
Energy Saving Control Filter Time Constant
s
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
46.2
38.91
38.91
36.23
36.23
32.79
32.79
30.13
C5-17 (C5-37) Motor Inertia
kgm
2
0.900
1.100
1.10
1.90
1.90
2.10
2.10
3.30
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01) Motor Rated Current
A
130
156
156
190
190
223
223
270
E2-02 (E4-02) Motor Rated Slip
Hz
1.39
1.4
1.4
1.4
1.4
1.38
1.38
1.35
E2-03 (E4-03) Motor No-Load Current
A
36
40
40
49
49
58
58
70
E2-05 (E4-05) Motor Line-to-Line Resistance
Ω
0.092
0.056
0.056
0.046
0.046
0.035
0.035
0.029
E2-06 (E4-06) Motor Leakage Inductance
%
20
20
20
20
20
20
20
20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation
W
1600
1760
1760
2150
2150
2350
2350
2850
E5-01
Motor Code Selection (for PM Motors)
Hex.
1246
1246
1247
1247
1248
1248
1249
1249
L2-02
Momentary Power Loss Ride-Thru Time
s
1.3
1.5
1.5
1.7
1.7
1.7
1.7
1.8
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
1
1
1
1
1
1
1
1
L2-04
Momentary Power Loss Voltage Recovery
Time
s
300
300
300
300
300
300
300
300
L2-21
Low Input Voltage Detection Level
V
300
300
300
300
300
300
300
300
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
30
30
30
30
30
30
30
30
n5-02
Motor Acceleration Time
s
0.533
0.592
0.592
0.646
0.646
0.673
0.673
0.777
Table B.16 400 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No.
Name
Unit
Default Settings
–
Drive Model
–
4
o
0361
4
o
0414
4
o
0477
4
o
0590
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
A9
AA
AC
AD
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
185
(250)
220
(300)
220
(300)
260
(350)
260
(350)
300
(400)
300
(400)
375
(500)
b3-04
V/f Gain during Speed Search
%
60
60
60
60
60
60
60
60
b3-06
Output Current 1 during Speed Search
–
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
b8-03
Energy Saving Control Filter Time Constant
s
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
30.13
30.57
30.57
27.13
27.13
21.76
21.76
21.76
C5-17 (C5-37) Motor Inertia
kgm
2
3.30
3.60
3.60
4.10
4.10
6.50
6.50
11.00
C6-02
Carrier Frequency Selection
–
1
1
1
1
0
0
0
0
E2-01 (E4-01) Motor Rated Current
A
270
310
310
370
370
500
500
500
E2-02 (E4-02) Motor Rated Slip
Hz
1.35
1.3
1.3
1.3
1.3
1.25
1.25
1.25
E2-03 (E4-03) Motor No-Load Current
A
70
81
81
96
96
130
130
130
E2-05 (E4-05) Motor Line-to-Line Resistance
Ω
0.029
0.025
0.025
0.02
0.02
0.014
0.014
0.014
E2-06 (E4-06) Motor Leakage Inductance
%
20
20
20
20
20
20
20
20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation
W
2850
3200
3200
3700
3700
4700
4700
4700
B.18 Defaults by Drive Model and Duty Rating ND/HD
592
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual