Drive Motor Overload Protection
Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor
overload protection is UL Listed and in accordance with the NEC and CEC.
n
E2-01: Motor Rated Current
Setting Range: 10% to 150% of the drive rated current
Default Setting: Model-dependent
Parameter E2-01 protects the motor when parameter L1-01 is not set to 0. The default for L1-01 is 1, which enables protection
for standard induction motors.
If Auto-Tuning has been performed successfully, the motor data entered to T1-04 and T2-06 are automatically written to
parameter E2-01. If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01.
n
L1-01: Motor Overload Protection Selection
The drive has an electronic overload protection function (oL1) based on time, output current, and output frequency that protects
the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external
thermal relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.
Table D.11 Overload Protection Settings
Setting
Description
0
Disabled
Disabled the internal motor overload protection of the drive.
1
Standard fan-cooled motor (default)
Selects protection characteristics for a standard self-cooled motor with limited
cooling capabilities when running below the rated speed. The motor overload
detection level (oL1) is automatically reduced when running below the motor rated
speed.
2
Drive duty motor with a speed range of 1:10
Selects protection characteristics for a motor with self-cooling capability within a
speed range of 10:1. The motor overload detection level (oL1) is automatically
reduced when running below 1/10 of the motor rated speed.
3
Vector motor with a speed range of 1:100
Selects protection characteristics for a motor capable of cooling itself at any speed
including zero speed (externally cooled motor). The motor overload detection level
(oL1) is constant over the entire speed range.
4
Permanent Magnet motor with variable torque
Selects protection characteristics for a variable torque PM motor. The motor
overload detection level (oL1) is automatically reduced when running below the
motor rated speed.
5
Permanent Magnet motor with constant torque
Selects protection characteristics for a constant torque PM motor. The motor
overload detection level (oL1) is constant over the whole speed range.
6
Standard fan-cooled motor (50 Hz)
Selects protection characteristics for a standard self-cooled motor with limited
cooling capabilities when running below the rated speed. The motor overload
detection level (oL1) is automatically reduced when running below the motor rated
speed.
When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection
(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01 = 1 to 6) when connecting the drive to a single motor, unless another motor overload
preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output
of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive
is powered up.
n
L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is running
a hot motor at 60 Hz and at 150% of the full load amp rating (E2-01) of the motor. Adjusting the value of L1-02 can shift the
set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
D.3 UL and CSA Standards
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
669
D
Standards Compliance