n
b3-06: Output Current 1 during Speed Search (Speed Estimation Type)
Sets the current injected to the motor at the beginning of Speed Estimation Speed Search as a factor of the motor rated current
set in E2-01 (E4-01 for motor 2). If the motor speed is relatively slow when the drive starts to perform Speed Search after a
long period of baseblock, it may be helpful to increase the setting value. The output current during Speed Search is automatically
limited by the drive rated current.
No.
Name
Setting Range
Default
b3-06
Output Current 1 during Speed Search
0.0 to 2.0
Determined by
o2-04
Note:
Use Current Detection Speed Search 2 if Speed Estimation is not working correctly even after adjusting b3-06.
n
b3-08: Current Control Gain during Speed Search (Speed Estimation Type)
Sets the proportional gain for the current controller to adjust the responsiveness during Speed Estimation Speed Search. There
is normally no need to change this parameter from the default value.
No.
Name
Setting Range
Default
b3-08
Current Control Gain during Speed Search (Speed Estimation Type)
0.00 to 6.00
A1-02 = 0 to 3:
Determined by
o2-04
A1-02 = 5, 6: 0.30
n
b3-10: Speed Search Detection Compensation Gain (Speed Estimation Type)
Sets the gain for the detected motor speed of the Speed Estimation Speed Search. Increase the setting only if an overvoltage
fault occurs when the drive restarts the motor.
No.
Name
Setting Range
Default
b3-10
Speed Search Detection Compensation Gain
1.00 to 1.20
1.05
n
b3-14: Bi-Directional Speed Search Selection (Speed Estimation Type, Speed Estimation 2
Type, Current Detection 3 Type)
Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search.
Disable this parameter when b3-50, Backspin Search Direction Judgment Time 1, is set to 0.1 or longer.
No.
Parameter Name
Setting Range
Default
b3-14
Bi-Directional Speed Search Selection
0, 1
Determined by
A1-02
Setting 0: Disabled
The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.
Setting 1: Enabled
The drive detects the motor rotation direction to restart the motor.
n
b3-17: Speed Search Restart Current Level (Speed Estimation Type)
Sets the current level at which Speed Estimation is restarted as a percentage of drive rated current to avoid overcurrent and
overvoltage problems since a large current can flow into the drive if the difference between the estimated frequency and the
actual motor speed is too big when performing Speed Estimation.
No.
Name
Setting Range
Default
b3-17
Speed Search Restart Current Level
0 to 200%
150%
n
b3-18: Speed Search Restart Detection Time (Speed Estimation Type)
Sets the time for which the current must be above the level set in b3-17 before restarting Speed Search.
No.
Name
Setting Range
Default
b3-18
Speed Search Restart Detection Time
0.00 to 1.00 s
0.10 s
5.2 b: Application
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
201
5
Parameter Details
Содержание U1000 iQpump Drive
Страница 705: ......