H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
LCD Display
Description
Page
37
During frequency output During RUN 2
All Modes
Open: No frequency output from drive if stopped with baseblock or DC injection
braking during initial excitation.
Closed: Drive is outputting a frequency.
38
Drive enabled
Drive Enable
All Modes
Closed: Multi-function input set for “Drive enable” is closed (H1-
oo
= 6A)
39
Power Consumption
Pulse Output
Energy Pulse Out
All Modes
Outputs a pulse to indicate the power consumption. Output units are determined
by H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
3A
Regenerated Power
Pulse Output
RegEn Pulse Out
All Modes
Outputs a pulse to indicate the regenerated power. Output units are determined by
H2-06. Outputs a pulse every 200 ms to indicate the kWh count.
3C
LOCAL/REMOTE
status
Local
All Modes
Open: REMOTE
Closed: LOCAL
3D
During speed search
During SpdSrch
All Modes
Closed: Speed Search is being executed.
3E
PID feedback low
PID Feedback Low
All Modes
Closed: PID feedback level is too low.
3F
PID feedback high
PID FeedbackHigh
All Modes
Closed: The PID feedback level is too high.
4C
During fast stop
During Fast Stop
All Modes
Closed: A Fast Stop command has been entered from the operator or input
terminals.
4D
oH Pre-alarm time limit OH Pre-Alarm
All Modes
Closed: oH pre-alarm time limit has passed.
60
Internal cooling fan
alarm
Fan Alrm Det
All Modes
Closed: Internal cooling fan alarm
61
Rotor position detection
completed
RotPosDetCmpIt
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
CLV/PM
Closed: Drive has successfully detected the rotor position of the PM motor.
62
MEMOBUS Register 1
(Selected with H2-07
and H2-08)
Memobus Regs1
All Modes
The contact output is closed when any of the bits specified by H2-08 for the
MEMOBUS/Modbus register address set in H2-07 turn on.
63
MEMOBUS Register 2
(Selected with H2-09
and H2-10)
Memobus Regs2
All Modes
The contact output is closed when any of the bits specified by H2-10 for the
MEMOBUS/Modbus register address set in H2-09 turn on.
64
During Commercial
Power Operation
CommerclPwr Mode
V/f
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f
OLV/PM
AOLV/PM
CLV/PM
V/f
V/f w PG
OLV
CLV
V/f w PG
OLV
CLV
Closed: Operating on commercial power.
90 to 92 DriveWorksEZ
digital outputs 1 to 3
–
All Modes
Reserved for DWEZ digital output functions.
100 to
192
Function 0 to 92 with
inverse output
!Function
All Modes
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1
oo
to reverse the output signal of that specific function.
B.9 H Parameters: Multi-Function Terminals
542