H1 Multi-Function Digital Input Selections
H1-
oo
Setting
Function
LCD Display
Description
Page
43
FWD/REV command
(2-Wire sequence 2)
FWD/REV 2WireSeq
All Modes
Open: Forward
Closed: Reverse
Note:
Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
44
Offset frequency 1
Offset Freq 1
All Modes
Closed: Adds d7-01 to the frequency reference.
45
Offset frequency 2
Offset Freq 2
All Modes
Closed: Adds d7-02 to the frequency reference.
46
Offset frequency 3
Offset Freq 3
All Modes
Closed: Adds d7-03 to the frequency reference.
47
Node setup
CanOpenNID Setup
All Modes
Closed: Node setup for SI-S3 enabled.
60
DC Injection Braking
command
DCInj Activate
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Triggers DC Injection Braking.
61
External Speed Search
command 1
Speed Search 1
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
AOLV/PM
OLV
Closed: Activates Current Detection Speed Search from the maximum output
frequency (E1-04).
62
External Speed Search
command 2
Speed Search 2
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
AOLV/PM
OLV
Closed: Activates Current Detection Speed Search from the frequency reference.
63
Field weakening
Field Weak
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
67
Communications test
mode
Comm Test Mode
All Modes
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays “PASS” if the
test completes successfully.
6A
Drive enabled
Drive Enable
All Modes
Open: Drive disabled. If this input is opened during run, the drive will stop as
specified by b1-03.
Closed: Ready for operation.
71
Speed/Torque control
Sswitch
Spd/Trq Ctl Chng
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Open: Speed Control
Closed: Torque Control
72
Zero servo
Zero Servo Cmd
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Closed: Zero Servo enabled
75
Up 2 command
Up Command 2
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2
function. The Up 2 and Down 2 commands must always be used in conjunction
with one another.
76
Down 2 command
Down Command 2
All Modes
Used to control the bias added to the frequency reference by the Up/Down 2
function. The Up 2 and Down 2 commands must always be used in conjunction
with one another.
77
ASR gain switch
ASR Gain Switch
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
CLV/PM
CLV
Open: ASR proportional gain 1 (C5-01)
Closed: ASR proportional gain 2 (C5-03)
B.9 H Parameters: Multi-Function Terminals
538