No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H3-16
(02F0) Terminal A1 Offset
TerminalA1Offset
All Modes
Adds an offset when the analog signal to terminal A1 is at 0 V.
Default: 0
Min.: -500
Max.: 500
H3-17
(02F1) Terminal A2 Offset
TerminalA2Offset
All Modes
Adds an offset when the analog signal to terminal A2 is at 0 V.
Default: 0
Min.: -500
Max.: 500
H3-18
(02F2) Terminal A3 Offset
TerminalA3Offset
All Modes
Adds an offset when the analog signal to terminal A3 is at 0 V.
Default: 0
Min.: -500
Max.: 500
H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
LCD Display
Description When Output Is 100%
Page
0
Frequency bias
Freq Ref Bias
All Modes
E1-04 (maximum output frequency)
1
Frequency gain
Freq Ref Gain
All Modes
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
of -100 to 0%.
2
Auxiliary frequency
reference 1
Aux Reference1
All Modes
E1-04 (maximum output frequency)
3
Auxiliary frequency
reference 2
Aux Reference2
All Modes
E1-04 (maximum output frequency)
4
Output voltage bias
Voltage Bias
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
10 V = E1-05 (motor rated voltage)
5
Accel/decel time gain
Acc/DecTime Gain
All Modes
10 V = 100%
6
DC Injection Braking
current
DC Brake Current
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
OLV
10 V = Drive rated current
7
Torque detection level
Torque Det Level
All Modes
10 V = Drive rated current (V/f, V/f w PG)
10 V = Motor rated torque (OLV, CLV, OLV/PM, AOLV/PM, CLV/PM)
8
Stall Prevention level
during run
Stall Prev Level
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
V/f
V/f w PG
10 V = Drive rated current
9
Output frequency lower
limit level
Ref Lower Limit
All Modes
10 V = E1-04 (maximum output frequency)
B
PID feedback
PID Feedback1
All Modes
10 V = 100%
C
PID setpoint
PID Set Point
All Modes
10 V = 100%
D
Frequency bias
Freq Ref Bias 2
All Modes
10 V = E1-04 (maximum output frequency)
E
Motor temperature
(PTC input)
Motor PTC
All Modes
10 V = 100%
F
Through mode
Not Used
All Modes
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
10
Forward torque limit
Fwd Torque Limit
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
AOLV/PM
OLV
CLV/PM
CLV
10 V = Motor rated torque
B.9 H Parameters: Multi-Function Terminals
544