n
Minor Faults and Alarms
for an overview of possible alarm codes. Conditions such as overvoltages can trip faults and alarms. It is
important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger a
digital output programmed for alarm output (H2-
oo
= 10). A fault (not an alarm) is present if the ALM LED lights without
blinking.
for information on fault codes.
Table 6.10 Minor Fault and Alarm Displays
Digital Operator
Display
Name
Minor Fault
Output
(H2-
oo
=
10)
Page
AEr
Station Address Setting Error
(CC-Link, CANopen,
MECHATROLINK)
YES
AUv
Power Supply Undervoltage
YES
bb
Baseblock
bUS
Option Card Communications
Error
YES
CALL Serial Communication
Transmission Error
YES
CE
MEMOBUS/Modbus
Communication Error
YES
CrST Cannot Reset
YES
CyC
MECHATROLINK Comm.
Cycle Setting Error
YES
dEv
Excessive Speed Deviation
(for Control Mode with PG)
YES
dnE
Drive Disabled
YES
doH
Damping Resistor Overheat
YES
dWAL DriveWorksEZ Fault
YES
E5
MECHATROLINK Watchdog
Timer Error
YES
EF
Forward/Reverse Run Command
Input Error
YES
EF0
Option Card External Fault
YES
to
EF1 to
EF8
External Fault
(input terminal S1 to S8)
YES
FAn
Fan Fault
YES
FbH
Excessive PID Feedback
YES
FbL
PID Feedback Loss
YES
Fdv
Power Supply Frequency Fault
YES
Hbb
Safe Disable Signal Input
YES
HbbF Safe Disable Signal Input
YES
Digital Operator
Display
Name
Minor Fault
Output
(H2-
oo
=
10)
Page
HCA
Current Alarm
YES
LT-1
Cooling Fan Maintenance Time No output
LT-2
Capacitor Maintenance Time
No output
LT-3
Soft Charge Bypass Relay
Maintenance Time
No output
oH
Heatsink Overheat
YES
oH2
Heatsink Overheat Warning
YES
oH3
Motor Overheat
YES
oL3
Overtorque 1
YES
oL4
Overtorque 2
YES
oL5
Mechanical Weakening
Detection 1
YES
oS
Overspeed
YES
ov
Control Circuit Overvoltage
YES
PASS MEMOBUS/Modbus Test Mode
Complete
No output
PGo
PG Disconnect
(for Control Mode with PG)
YES
PGoH PG Hardware Fault
(when using PG-X3)
YES
rUn
Motor Switch during Run
YES
SE
MEMOBUS/Modbus Test Mode
Fault
YES
SrC
Phase Order Detection Fault
YES
UL3
Undertorque Detection 1
YES
UL4
Undertorque Detection 2
YES
UL5
Mechanical Weakening
Detection 2
YES
Uv
Control Circuit Undervoltge
YES
<1> Output when H2-
<2> Baseblock alarm “bb” will not activate a digital output programmed for minor fault H2-0
= 8 or 1B to activate a digital otuput
6.3 Drive Alarms, Faults, and Errors
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
365
6
Troubleshooting
Содержание U1000 iQpump Drive