![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 170](http://html1.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_technical-manual_3309131170.webp)
No.
Name
Setting Range
Default
T3-03
Motor Inertia
0.0001 to 600.00 kgm
2
Determined by o2-04,
C6-01, E5-01
Note:
Display is in the following units:
Models 4
o
0011 and 4
o
0014: 0.0001 kgm
2
units
Models 2
o
0028 to 2
o
0192 and 4
o
0021 to 4
o
0124: 0.001 kgm
2
units
Models 2
o
0248 and 4
o
0156 to 4
o
0930: 0.01 kgm
2
units
Display resolution depends on the rated output current of the drive after setting drive duty using parameter C6-01.
n
T3-04: ASR Response Frequency
Sets the response frequency (reciprocal of the step response time constant) of the system or the connected machine. The drive
uses this value and the load inertia to fine-tune the speed control loop gain (C5-01, ASR Gain 1). Oscillation may result if the
value input here is higher than the actual response frequency of the system.
No.
Name
Setting Range
Default
T3-04
ASR Response Frequency
0.1 to 50.0 Hz
10.0 Hz
4.7 Auto-Tuning
170
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual