No.
Parameter Name
Setting Range
Default
C5-28
Motor 2 ASR Integral Limit
0 to 400%
400%
n
C5-32: Integral Operation during Accel/Decel for Motor 2
Functions for motor 2 the same way that C5-12 functions for motor 1. Enables integral operation during acceleration and
Refer to C5-12: Integral Operation during Accel/Decel (V/f w/PG) on page 231
No.
Parameter Name
Setting Range
Default
C5-32
Integral Operation during Accel/Decel for Motor 2
0, 1
0
Setting 0: Disabled
Integral operation occurs only during constant speed and not during acceleration or deceleration.
Setting 1: Enabled
Integral operation is always enabled.
n
C5-37, C5-38: Motor 2 Inertia, Motor 2 Load Inertia Ratio
These parameters function for motor 2 the same way that C5-17 and C5-18 function for motor 1. These parameters are set
for details on Auto-Tuning or enter the data manually.
No.
Parameter Name
Setting Range
Default
C5-37
Motor 2 Inertia
0.0001 to 600.00 kgm
2
Determined by C6-01 and
o2-04
C5-38
Motor 2 Load Inertia Ratio
0.0 to 6000.0
1.0
u
C6: Carrier Frequency
n
C6-01: Drive Duty Mode Selection
The drive has two different duty modes from which to select based on the load characteristics. The drive rated current, overload
capacity, and maximum output frequency will change depending upon the duty mode selection. Use parameter C6-01 to select
Heavy Duty (HD) or Normal Duty (ND) for the application.
Refer to Heavy Duty and Normal Duty Ratings on page 476
for details about the rated current.
No.
Parameter Name
Setting Range
Default
C6-01
Duty Mode Selection
0, 1
1 (ND)
Table 5.16 Differences between Heavy Duty and Normal Duty
Characteristics
Heavy Duty Rating (HD)
Normal Duty Rating (ND)
C6-01
0
1
Performance
100 %
100 %
0
Motor Speed
Rated Load
Overload
150 %
Motor Speed
0
100 %
100 %
120 %
Rated Load
Overload
Application
Use Heavy Duty Rating for applications requiring a high
overload tolerance with constant load torque, such as
extruders and conveyors.
Use Normal Duty Rating for applications in which the torque
requirements drop along with the speed, such as fans and
pumps where a high overload tolerance is not required.
Overload capability (oL2)
150% of drive rated Heavy Duty current for 60 s
120% of drive rated Normal Duty current for 60 s
Stall Prevention during
Acceleration (L3-02)
150%
120%
Stall Prevention during
Run (L3-06)
150%
120%
Default Carrier Frequency
4 kHz
5.3 C: Tuning
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
233
5
Parameter Details
Содержание U1000 iQpump Drive
Страница 705: ......