Setting 6A: Drive Enable
A digital input configured as a “Drive enable” (H1-
oo
= 6A) will prevent the drive from executing a Run command until
the input is closed. When the input is open, the digital operator will display “dnE” to indicate that the drive is disabled.
If a Run command is enabled before the terminal set for “Drive enable” closes, then the drive will not run until the Run
command is cycled (i.e., a new Run command is required). If the input is opened while the drive is running, the drive will stop
according to the stop method set to b1-03 (
Refer to b1-03: Stopping Method Selection on page 189
).
Setting 71: Speed/Torque Control Switch
Switches the drive between Torque Control and Speed Control. Torque Control is enabled when the terminal is closed, and
Speed Control is enabled when the terminal is open. Set parameter d5-01 to 0 when using this function.
Switching Between Torque and Speed Control
.
Setting 72: Zero Servo
Activates the Zero Servo function to lock the rotor at a certain position.
Refer to b9: Zero Servo on page 220
for details.
Setting 75, 76: Up 2/Down 2 Function
The Up/Down 2 function adds a bias to the frequency reference. The input programmed for 75 will increase the bias and the
input programmed for 76 will decrease the bias.
explains how the Up/Down 2 function works depending on the
frequency reference source and parameters d4-01, d4-03, and d4-05.
Refer to d4: Frequency Reference Hold and Up/Down
for detailed explanations of these and other Up/Down 2 related parameters.
Note:
1.
The Up/Down 2 functions must be set as a pair.
2.
When using the Up/Down 2 function, set appropriate bias limit values to parameters d4-08 and d4-09.
Table 5.40 Up/Down 2 Operations
Condition
Freq. Ref.
Source
d4-03
d4-05
d4-01
Operation
Frequency Saved
1
Multi-Step Speed
Reference
0
0
0
• Accelerates (increases the bias) while the Up 2
terminal is closed.
• Decelerates (decreases the bias) while Down 2 is
closed.
• Holds output frequency (holds the bias) when no
Up 2 or Down 2 input or both active.
• Resets the bias when the reference changes.
• Operates with the frequency reference in all other
situations.
Not saved
2
1
If the bias and frequency reference
are constant for 5 s, the bias is
added to the active frequency
reference and reset afterwards.
3
1
--
• Accelerates (increases the bias) while the Up 2
terminal is closed.
• Decelerates (decreases the bias) while Down 2 is
closed.
• Otherwise operates at the frequency reference.
Not saved
4
Multi-Step Speed
Reference
Value
other
than 0
--
0
• When the Up 2 is enabled, the drive accelerates to
the frequency reference plus d4-03 (bias is
increased for d4-03).
• When Down 2 is enabled, the drive decelerates to
the frequency reference minus d4-03 (bias is
decreased for d4-03).
• Holds output frequency (holds the bias) when
neither Up/Down 2 inputs are active or both inputs
are active.
• Resets the bias when the reference changes.
• Operates with the frequency reference in all other
situations.
Not saved
5
1
If the bias and frequency reference
are constant for 5 s, the bias is
added to the active frequency
reference and reset afterwards.
6
Other (analog
comm., etc.)
0
0
0
• Accelerates (increases the bias) while the Up 2
terminal is closed.
• Decelerates (decreases the bias) while Down 2 is
closed.
• Holds output frequency (holds the bias) when
neither Up/Down 2 inputs are active or both inputs
are active.
• If the frequency reference changes for more than
the time set to d4-07 during accel/decel, bias value
is held until the output frequency meets the
reference (speed agree).
Not saved
7
1
If the bias is constant for 5 s, it is
saved to parameter d4-06. The
frequency reference cannot be
overwritten, so only the bias is
saved.
5.7 H: Terminal Functions
286