No.
Parameter Name
Setting Range
Default
F6-21
MECHATROLINK Frame Size
0, 1
0
Setting 0: 32-byte (MECHATROLINK-II option setting)
Value for MECHATROLINK-III option is: 64-byte
Setting 1: 17-byte (MECHATROLINK-II option setting)
Value for MECHATROLINK-III option is: 32-byte
n
F6-22: MECHATROLINK Link Speed
Sets the communication speed for a MECHATROLINK-II option card.
Note:
This parameter is only available with a MECHATROLINK-II option card.
No.
Parameter Name
Setting Range
Default
F6-22
MECHATROLINK Link Speed
0, 1
0
Setting 0: 10 Mbps
Setting 1: 4 Mbps
n
F6-23: MECHATROLINK Monitor Selection (Code 0EH)
Sets MEMOBUS/Modbus register to monitor SEL_MON of INV_CTL and INV_CTL.
Setting byte 10 of INV_CTL to “0EH” enables the register set by F6-23.
Bytes 11 and 12 of the response data enable the register content set by F6-23.
No.
Parameter Name
Setting Range
Default
F6-23
MECHATROLINK Monitor Selection (Code 0EH)
0 to FFFFH
0H
n
F6-24: MECHATROLINK Monitor Selection (Code 0FH)
Sets MEMOBUS/Modbus register to monitor SEL_MON of INV_CTL and INV_CTL.
Setting byte 10 of INV_CTL to 0FH enables the register set by F6-24.
Bytes 11 and 12 of the response data enable the register content set by F6-24.
No.
Parameter Name
Setting Range
Default
F6-24
MECHATROLINK Monitor Selection (Code 0FH)
0 to FFFFH
0H
n
F6-25: Operation Selection at Watchdog Error (E5)
No.
Parameter Name
Setting Range
Default
F6-25
Operation Selection at Watchdog Error (E5)
0 to 3
1
Setting 0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
Setting 1: Coast to stop
Setting 2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
Setting 3: Alarm only
n
F6-26: MECHATROLINK bUS Errors Detected
No.
Parameter Name
Setting Range
Default
F6-26
MECHATROLINK bUS Errors Detected
2 to 10
2
u
PROFIBUS-DP Parameters
Parameters F6-30 through F6-32 set the drive to run on a PROFIBUS-DP network.
n
F6-30: PROFIBUS-DP Node Address
Sets the node address of a PROFIBUS-DP option card.
5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
273
5
Parameter Details