n
Single Drive Installation
show the installation distance required to maintain sufficient space for airflow and wiring.
Drive Models 2
o
0028 to 2
o
0248 and 4
o
0011 to 4
o
0590
A
C
A
B
B
D
E
Side Clearance
Top/Bottom Clearance
A – 50 mm (1.97 in) minimum
B – 30 mm (1.18 in) minimum
C – 200 mm (7.87 in) minimum
D – 120 mm (4.72 in) minimum
E – Airflow direction
Figure 2.2 Correct Drive Installation Spacing
Note:
IP20/UL Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for
installation.
Drive Models 4
o
0720 to 4
o
0930 and Harmonic Filter Module
Side Clearance
Top/Bottom Clearance
A
A
C
B
B
E
D
F
Drive Model
Harmonic
Filter Module
4
o
0720
A – 50 mm (1.97 in) minimum
B – 30 mm (1.18 in) minimum
C – 200 mm (7.87 in) minimum
D – 120 mm (4.72 in) minimum
E – 60 mm (2.36 in) minimum
F – Airflow direction
Figure 2.3 Correct Drive Model 4
o
0720 and Harmonic Filter Module Installation Spacing
2.2 Mechanical Installation
60
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive