B.18 Defaults by Drive Model and Duty Rating ND/HD
The following tables show parameters and default settings that change with the drive model selection (o2-04) and drive duty
selection (C6-01). Parameter numbers shown in parenthesis are valid for motor 2.
Table B.9 200 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No.
Name
Unit
Default Settings
–
Drive Model
–
2
o
0028
2
o
0042
2
o
0054
2
o
0068
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
6A
6B
6D
6E
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
5.5 (7.5) 7.5 (10) 7.5 (10)
11 (15)
11 (15)
15 (20)
15 (20) 18.5 (25)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
94.75
72.69
72.69
70.44
70.44
63.13
63.13
57.87
C5-17 (C5-37) Motor Inertia
kgm
2
0.026
0.037
0.037
0.053
0.053
0.076
0.076
0.138
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01) Motor Rated Current
A
19.6
26.6
26.6
39.7
39.7
53
53
65.8
E2-02 (E4-02) Motor Rated Slip
Hz
1.5
1.3
1.3
1.7
1.7
1.6
1.6
1.67
E2-03 (E4-03) Motor No-Load Current
A
5.1
8
8
11.2
11.2
15.2
15.2
15.7
E2-05 (E4-05) Motor Line-to-Line Resistance
Ω
0.399
0.288
0.288
0.23
0.23
0.138
0.138
0.101
E2-06 (E4-06) Motor Leakage Inductance
%
18.2
15.5
15.5
19.5
19.5
17.2
17.2
20.1
E2-10 (E4-10) Motor Iron Loss for Torque Compensation
W
172
262
262
245
245
272
272
505
E5-01
Motor Code Selection (for PM Motors)
Hex.
120A
120A
120B
120B
120D
120D
120E
120E
L2-02
Momentary Power Loss Ride-Thru Time
s
0.7
0.8
0.8
0.9
0.9
1
1
1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s
0.3
0.3
0.3
0.3
0.3
0.6
0.6
0.6
L2-04
Momentary Power Loss Voltage Recovery
Time
s
150
150
150
150
150
150
150
150
L2-21
Low Input Voltage Detection Level
V
150
150
150
150
150
150
150
150
L8-02
Overheat Alarm Level
°C
130
130
130
130
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
10
n5-02
Motor Acceleration Time
s
0.168
0.175
0.175
0.265
0.265
0.244
0.244
0.317
Table B.10 200 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No.
Name
Unit
Default Settings
–
Drive Model
–
2
o
0081
2
o
0104
2
o
0130
2
o
0154
C6-01
Drive Duty Selection
–
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex.
6F
70
72
73
E2-11
(E4-11)
Motor Rated Output
kW
(HP) 18.5 (25) 22 (30)
22 (30)
30 (40)
30 (40)
37 (50)
37 (50)
45 (60)
b3-04
V/f Gain during Speed Search
%
100
100
100
80
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
57.87
51.79
51.79
46.27
46.27
38.16
38.16
35.78
C5-17 (C5-37) Motor Inertia
kgm
2
0.138
0.165
0.165
0.220
0.220
0.273
0.273
0.333
C6-02
Carrier Frequency Selection
–
1
1
1
1
1
1
1
1
E2-01 (E4-01) Motor Rated Current
A
65.8
77.2
77.2
105
105
131
131
160
E2-02 (E4-02) Motor Rated Slip
Hz
1.67
1.7
1.7
1.8
1.8
1.33
1.33
1.6
B.18 Defaults by Drive Model and Duty Rating ND/HD