u
F4: Analog Monitor Card Settings
These parameters set the drive for operation with the analog output option card AO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
n
F4-01, F4-03: Terminal V1, V2 Monitor Selection
Selects the data to output from analog terminal V1. Enter the final three digits of U
o
-
oo
to determine which monitor data
is output from the option card. Some monitors are only available in certain control modes.
No.
Parameter Name
Setting Range
Default
F4-01
Terminal V1 Monitor Selection
000 to 999
102
F4-03
Terminal V2 Monitor Selection
000 to 999
103
Note:
Set “000” or “031” when using the terminal in through mode. This setting can adjust the V1 and V2 terminal output from PLC via
MEMOBUS/Modbus communications or a communications option.
n
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Monitor Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set as
a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is limited to
10 V.
No.
Parameter Name
Setting Range
Default
F4-02
Terminal V1 Monitor Gain
-999.9 to 999.9%
100.0%
F4-04
Terminal V2 Monitor Gain
-999.9 to 999.9%
50.0%
F4-05
Terminal V1 Monitor Bias
-999.9 to 999.9%
0.0%
F4-06
Terminal V2 Monitor Bias
-999.9 to 999.9%
0.0%
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal V1
1.
View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in F4-01 will be output from terminal V1.
2.
Adjust F4-02 viewing the monitor connected to the terminal V1.
3.
View the value set to F4-05 on the digital operator, terminal V1 will output a voltage equal to 0% of the parameter
being set in F4-01.
4.
Adjust F4-05 viewing the output signal on the terminal V1.
Terminal V2
1.
View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being viewed in F4-03 will be output from terminal V2.
2.
Adjust F4-04 viewing the monitor connected to the terminal V2.
3.
View the value set to F4-06 on the digital operator, terminal V2 will output a voltage equal to 0% of the parameter
being set in F4-03.
4.
Adjust F4-06 viewing the output signal on the terminal V2.
n
F4-07, F4-08: Terminal V1, V2 Signal Level
Sets the output signal level for terminals V1 and V2.
No.
Parameter Name
Setting Range
Default
F4-07
Terminal V1 Signal Level
0, 1
0
F4-08
Terminal V2 Signal Level
0, 1
0
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
269
5
Parameter Details