Output Voltage
Output Voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Monitor Value
0%
H4-07, 08 = 0
H4-07, 08 = 1
10
V
-10 V
100%
5 V
15
V
-5 V
-15 V
-100%
Figure 5.84 Analog Output Gain and Bias Setting Example 1 and 2
Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
Monitor Value
Monitor Value
0 V
3 V
10 V
100%
0%
Output Voltage
Output Voltage
H4-07, 08 = 0
H4-07, 08 = 1
10V
-10 V
100%
3 V
-4 V
-100%
Figure 5.85 Analog Output Gain and Bias Setting Example 3
n
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
Set jumper S5 on the terminal board accordingly when changing these parameters.
Refer to Terminal AM/FM Signal
for details on setting S5.
No.
Name
Setting Range
Default
H4-07
Multi-Function Analog Output Terminal FM
Signal Level Selection
0 to 2
0
H4-08
Multi-Function Analog Output Terminal AM
Signal Level Selection
0 to 2
0
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
u
H5: MEMOBUS/Modbus Serial Communication
Serial communication is possible in the drive using the built-in RS-422/485 port (terminals R+, R-, S+, S-) and programmable
logic controllers (PLCs) or similar devices running the MEMOBUS/Modbus protocol.
The H5-
oo
parameters set the drive for MEMOBUS/Modbus Communications.
Refer to MEMOBUS/Modbus Serial
for detailed descriptions of the H5-
oo
parameters.
u
H6: Pulse Train Input/Output
A one-track pulse train signal with a maximum frequency of 32 kHz can be input to the drive at terminal RP. This pulse train
signal can be used as the frequency reference, for PID functions, or as the speed feedback signal in V/f Control.
5.7 H: Terminal Functions