C6-03
(0225)
Carrier Frequency Upper
Limit
CarrierFreq Max
All Modes
Note:
C6-04 and C6-05 are available only in V/f and
V/f w/PG control modes.
Determines the upper and lower limits for the carrier frequency.
In OLV, C6-03 determines the upper limit of the carrier
frequency.
Carrier Frequency
E1-04
Max Output
Frequency
Output Frequency
× (C6-05)
Output
Frequency
C6-03
C6-04
Note:
Setting range of C6-04 and C6-05 is 4.0 to 10.0
kHz for models 2
o
0028 to 2
o
0248, 4
o
0011 to
4
o
0414. Setting value is only 3 kHz for models
4
o
0477 to 4
o
0930.
Min.: 3.0 kHz
Max.: 10.0 kHz
C6-04
(0226)
Carrier Frequency
Lower Limit
CarrierFreq Min
Min.: 3.0 kHz
Max.: 10.0 kHz
C6-05
(0227)
Carrier Frequency
Proportional Gain
CarrierFreq Gain
Min.: 0
Max.: 99
C6-09
(022B)
Carrier Frequency
during Rotational Auto-
Tuning
Carrier in tune
0: Fc = 5kHz
1: Fc = C6-03
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
OLV
CLV/PM
CLV
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM
AOLV/PM
OLV
CLV/PM
CLV
0: Carrier Frequency = 4 kHz.
Note:
Carrier frequency is 3 kHz for models 4
o
0477
to 4
o
0930.
1: Setting value for C6-03.
Default: 0
Range: 0, 1
<1> Default setting value is determined by parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Setting range is determined by o2-04, Drive Model Selection.
Range is 1 to 4 and F in models 2
<3> Default setting value is determined by parameters C6-02, Carrier Frequency Selection, and o2-04, Drive Model Selection.
<4> Default setting value is determined by parameter C6-02, Carrier Frequency Selection.
u
C7: Voltage Adjustment
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
C7-43
(112A)
Input Voltage Offset
Adjustment
InputVolt Offset
All Modes
Adjusts the offset for the input voltage circuit when the control
board is replaced.
0000: Standard
0002: Offset adjustment not required
Default: 0000
Range: 0000 to
9999
C7-56
(1107)
Power Factor Control
Selection
PF Control Sel
0: PF Ctrl Disabled
1: PF Ctrl Enabled
All Modes
0: Power factor control disabled
1: Power factor control enabled
Default: 0
Range: 0, 1
C7-60
(0B1C)
Output Voltage Limit
Mode Selection
V Out Limit Sel
0: Limit Harmonics
1: Improve PF
All Modes
0: Harmonic suppression priority mode
1: High output voltage mode
Default: 1
Range: 0, 1
B.5 C: Tuning
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
509