U1-05: motor speed
U1-16: output frequency after softstarter (accel/decel ramp generator)
d1-01 to d1-17: frequency references
2.
Setting o1-03 to 2 requires entering the number of motor poles to E2-04, E4-04, and E5-04.
n
o1-04: V/f Pattern Display Unit
Determines the units used for the frequency reference when setting parameters that create the V/f pattern: E1-04, E1-06, E1-09,
E1-11, and E2-04. For motor 2, this includes parameters E3-04, E3-06, E3-07, E3-09, and E3-11. Enabled only in vector
control modes (CLV, AOLV/PM, CLV/PM).
No.
Name
Setting Range
Default
o1-04
V/f Pattern Display Unit
0, 1
0
Setting 0: Hertz
Setting 1: r/min
Note:
For motor 2, o1-04 can only be set to 0 for Hertz.
n
o1-05: LCD Contrast Control
Sets the brightness of the digital operator. The lower the setting, the brighter the LCD contrast. The higher the setting, the
darker the LCD contrast.
No.
Name
Setting Range
Default
o1-05
LCD Contrast Control
0 to 5
3
n
o1-10: User-Set Display Units Maximum Value
Determines the display value that is equal to the maximum output frequency.
No.
Name
Setting Range
Default
o1-10
User-Set Display Units Maximum Value
1 to 60000
Determined by
o1-03
n
o1-11: User-Set Display Units Decimal Display
Determines how many decimal points should be used to set and display the frequency reference.
No.
Name
Setting Range
Default
o1-11
User-Set Display Units Decimal Display
0 to 3
Determined by
o1-03
Setting 0: No Decimal Point
Setting 1: One Decimal Point
Setting 2: Two Decimal Points
Setting 3: Three Decimal Points
u
o2: Digital Operator Keypad Functions
These parameters determine the functions assigned to the operator keys.
n
o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection
Determines whether the LO/RE key on the digital operator will be enabled for switching between LOCAL and REMOTE.
No.
Name
Setting Range
Default
o2-01
LO/RE Key Function Selection
0, 1
1
Setting 0: Disabled
The LO/RE key is disabled.
Setting 1: Enabled
The LO/RE switches between LOCAL and REMOTE operation. Switching is possible during stop only. When LOCAL is
selected, the LED indicator on the LO/RE key will light up.
5.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
345
5
Parameter Details